Every observation on an Electrical Installation Condition Report is given a code. Any C1, C2 or FI makes the report unsatisfactory; C3 is a recommendation only. The inspector makes the final call on site, because context matters.
C1: danger present
Something could hurt someone now, such as exposed live parts from a broken socket or a missing cover. The inspector makes it safe before leaving, usually by isolating the circuit or replacing the accessory.
C2: potentially dangerous
Urgent repair is needed. Typical C2 findings in Nottingham homes include:
- Scorch marks or heat damage at a socket or switch, often from a loose connection or overload
- No main earth bonding to gas or water pipes, often disturbed during kitchen or bathroom refits
- Metal light fittings on a pre-1966 lighting circuit with no earth
- No RCD on sockets that could power outdoor equipment
- A DIY shed or garage supply with unprotected cable
FI: further investigation
Test results point to a problem the inspector couldn’t trace in the time available, for example damp in a cellar or old cable under floors. It must be investigated within 28 days, and the report stays unsatisfactory until it is resolved.
C3: improvement recommended
C3 items don’t fail the report. An older plastic consumer unit in good condition or missing circuit labels on the fusebox are common examples: worth fixing, but with no legal deadline.
Deadlines for rented homes
Remedial work or investigation for any C1, C2 or FI item must be completed within 28 days, or a shorter period if the report says so. Try the code decoder on our home page to look up a specific finding.